                           Title: HEATING / AIR CONDITIONING: REFRIGERANT (for HFO-1234yf(R1234yf)): ON-VEHICLE INSPECTION; 2019 MY RAV4 RAV4 HV [11/2018 - 02/2019] | 
                      
                   
                  ON-VEHICLE INSPECTION
                   
                  PROCEDURE
                   
                  1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET 
                  HINT: 
                  The following examples show the readings of a manifold gauge set and the corresponding air conditioning system problems. 
                  (a) Read the manifold gauge pressure when the following conditions are met: 
                  
                     
                        - 
The doors are fully open.
 
                        - 
The engine is idling.
 
                        - 
The A/C switch is on.
 
                        - 
The temperature is set to max cold.
 
                        - 
The blower speed is set to high.
 
                        - 
The temperature at the air inlet with recirculate selected is 30 to 35°C (86 to 95°F).
 
                      
                   
                  
                     
                        
                           | 
                               (1) Normal functioning air conditioning system 
                              Gauge Reading
                              
                                 
                                 
                                 
                                    
                                       | 
                                           Pressure Side 
                                        | 
                                       
                                           Refrigerant Volume 
                                        | 
                                     
                                 
                                 
                                    
                                       | 
                                           Low 
                                        | 
                                       
                                           150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi) 
                                        | 
                                     
                                    
                                       | 
                                           High 
                                        | 
                                       
                                           1370 to 1570 kPa (14.0 to 16.0 kgf/cm2, 199 to 228 psi) 
                                        | 
                                     
                                 
                               
                            | 
                           
                              
                            | 
                         
                     
                   
                  (2) Abnormally functioning air conditioning system 
                   
                  
                  
                     
                        - 
During operation, pressure on low pressure side cycles between normal and vacuum
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system periodically cools and then fails to cool 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Moisture in air conditioning system freezes at expansion valve orifice, causing refrigerant to temporarily stop circulating 
                                     | 
                                  
                                 
                                    | 
                                        After system stops and warms up again, ice melts and normal operation is temporarily restored 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Cooler dryer (integrated into condenser tank) saturated with moisture 
                                     | 
                                  
                                 
                                    | 
                                        Moisture in air conditioning system is freezing at expansion valve orifice and blocking circulation of refrigerant 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Replace cooler dryer 
                                     | 
                                  
                                 
                                    | 
                                        Remove moisture by repeatedly evacuating air from air conditioning system 
                                     | 
                                  
                                 
                                    | 
                                        Recharge air conditioning system with proper amount of new or purified refrigerant 
                                     | 
                                  
                              
                            
                           HINT: 
                           For the example above, moisture is present in the air conditioning system. 
                         
                        - 
Pressure is low on both low and high pressure side
 
                           
                           
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system does not cool effectively 
                                     | 
                                  
                                 
                                    | 
                                        Insufficient cooling performance 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Refrigerant leaks from air conditioning system 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Insufficient refrigerant 
                                     | 
                                  
                                 
                                    | 
                                        Refrigerant leaking 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Check for refrigerant leaks and repair if necessary 
                                     | 
                                  
                                 
                                    | 
                                        Recharge air conditioning system with proper amount of new or purified refrigerant 
                                     | 
                                  
                                 
                                    | 
                                        If gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing leaks 
                                     | 
                                  
                              
                            
                           HINT: 
                           For the example above, there is insufficient refrigerant. 
                         
                        - 
Pressure is low on both low and high pressure side
 
                           
                           
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system does not cool effectively 
                                     | 
                                  
                                 
                                    | 
                                        Frost exists on pipe from condenser to evaporator unit 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Refrigerant flow is obstructed by dirt inside pipes of condenser core 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Condenser is clogged 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Replace condenser 
                                     | 
                                  
                              
                            
                           HINT: 
                           For the example above, there is poor circulation of refrigerant. 
                         
                        - 
Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side
 
                           
                           
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system does not cool effectively (System may cool occasionally) 
                                     | 
                                  
                                 
                                    | 
                                        Frost or condensation is seen on piping on both sides of receiver/dryer or expansion valve 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Refrigerant flow is obstructed by moisture or dirt in air conditioning system 
                                     | 
                                  
                                 
                                    | 
                                        Expansion valve is stuck closed 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Refrigerant does not circulate 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Replace expansion valve 
                                     | 
                                  
                                 
                                    | 
                                        Replace condenser 
                                     | 
                                  
                                 
                                    | 
                                        Evacuate air conditioning system and recharge with proper amount of new or purified refrigerant 
                                     | 
                                  
                              
                            
                           HINT: 
                           For the example above, the refrigerant does not circulate. 
                         
                        - 
Pressure is too high on both low and high pressure side
 
                           
                           
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system does not cool effectively 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Unable to provide sufficient performance due to excessive amount of refrigerant 
                                     | 
                                  
                                 
                                    | 
                                        Cooling effectiveness of condenser is insufficient 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Excessive amount of refrigerant in air conditioning system because excessive refrigerant was added during recharging 
                                     | 
                                  
                                 
                                    | 
                                        Cooling effectiveness of condenser is insufficient because condenser fins are clogged or cooling fan is faulty 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Clean condenser 
                                     | 
                                  
                                 
                                    | 
                                        Check operation of condenser cooling fan 
                                     | 
                                  
                                 
                                    | 
                                        If condenser is clean and fan operation is normal, check amount of refrigerant and recharge air conditioning system with proper amount of new or purified refrigerant 
                                     | 
                                  
                              
                            
                           HINT: 
                           For the example above, the air conditioning system is overcharged or cooling effectiveness of condenser is insufficient. 
                         
                        - 
Pressure is too high on both low and high pressure side
 
                           
                           
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system does not cool 
                                     | 
                                  
                                 
                                    | 
                                        The low pressure piping is too hot to touch 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Air in air conditioning system 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Air present in air conditioning system 
                                     | 
                                  
                                 
                                    | 
                                        Insufficient vacuum purging when evacuating air conditioning system 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Replace cooler dryer 
                                     | 
                                  
                                 
                                    | 
                                        Check compressor oil to see if it is dirty or insufficient 
                                     | 
                                  
                                 
                                    | 
                                        Evacuate air conditioning system and recharge it with new or purified refrigerant 
                                     | 
                                  
                              
                            
                           NOTICE: 
                           These gauge indications occur when the air conditioning system has been left open and then recharged without evacuating the system. 
                           HINT: 
                           For the example above, air is present in the air conditioning system. 
                         
                        - 
Pressure is too high on both low and high pressure side
 
                           
                           
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system does not cool effectively 
                                     | 
                                  
                                 
                                    | 
                                        Frost or large amount of condensation on piping on low pressure side 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Expansion valve may be stuck open or metering refrigerant incorrectly 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Excessive refrigerant in low pressure piping 
                                     | 
                                  
                                 
                                    | 
                                        Expansion valve open too wide 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Replace expansion valve 
                                     | 
                                  
                              
                            
                           HINT: 
                           For the example above, there is an expansion valve malfunction. 
                         
                        - 
Pressure is too high on both low and high pressure side or pressure is too low on high pressure side
 
                           
                           
                              
                                 
                                 
                              
                              
                                 
                                    | 
                                        Symptom 
                                     | 
                                    
                                        Air conditioning system does not cool effectively 
                                     | 
                                  
                                 
                                    | 
                                        Probable Cause 
                                     | 
                                    
                                        Internal leak in compressor 
                                     | 
                                  
                                 
                                    | 
                                        Diagnosis 
                                     | 
                                    
                                        Low compression 
                                     | 
                                  
                                 
                                    | 
                                        Leak from damaged valve or other compressor component 
                                     | 
                                  
                                 
                                    | 
                                        Corrective Actions 
                                     | 
                                    
                                        Replace compressor 
                                     | 
                                  
                              
                            
                           HINT: 
                           For the example above, there is insufficient compressor compression. 
                         
                      
                   
                  (3) Gauge readings (Reference) 
                   
                  
                     
                        
                        
                        
                        
                     
                     
                        
                           | 
                               *a 
                            | 
                           
                               Pressure on Low Pressure Side kPa (kgf/cm2, psi) 
                            | 
                           
                               *b 
                            | 
                           
                               Pressure on High Pressure Side kPa (kgf/cm2, psi) 
                            | 
                         
                        
                           | 
                               *c 
                            | 
                           
                               Blower High Zone 
                            | 
                           
                               *d 
                            | 
                           
                               Blower Low Zone 
                            | 
                         
                     
                   
                  
                |